80*80mm panel frequency meter (JY-6L2)


Anti-vibration and anti-shock:

Anti-vibration: Complies with the standard of IEC60068-2-6; Frequency sweep range: 10-55-10Hz; Displacement amplitude: ± 0.15mm, ± 0.3mm; Frequency sweep cycles: 5 times; Sweep rate: 10ct/min; Maximum acceleration: 147m/s2(15g), 490m/s2(50g); RMS acceleration: 6.06g; Vibration time: 15 min. Anti mechanical shock: Complies with the standard of IEC60068-2-27.

Accuracy level:

The JY series of pointer meter: AC and DC voltmeter and ammeter to the level of 1.5 or 2.5, power meter to the level of 2.5, frequency meter to the level of 2.5, and power factor meter to the level of 2.5.

Overload ammeter:

The conventional overload multiple times should be once or twice, and it can be customized to once, twice, 3 times and so on according to the user's requirements. Its function is to indicate the approximate transient overload current value, such as the start-up current when the motor stars, and so on.

Extrinsic current shunt:

The voltage specifications of the extrinsic current shunt of DC ammeters are 150mV, 100mV, 75mV, 60mV and 50mV, which can be customized. The resistance of the conducting wire connecting the meter and the current shunt should within the range of 1525mΩ , to ensure the accuracy of the meter.

The surface of the dial:

The surface of the dial uses aluminum alloy, white paint, black ink printing or laser printing. The dial can be customized according to the customer's sample dials (overprint colors can be customized). The luminous dial uses the PC panel.

Name

precision

normal specification

remark

AC ammeter

A

1.5

0.5-50A

can be directly connected

A

1.5

10/5A-800/5A
secondary current passed by current transformer

KA

1.5

1KA-10KA
secondary current passed by current transformer

AC voltmeter

V

1.5

10V-600V

can be directly connected

KV

1.5

1KV-35KV

100V secondary voltage passed by voltage transformer

DC ammeter

µA mA

2.5

50μA-500μA 1mA-500mA
can be directly connected

A

1.5

1A-15A

can be directly connected

A

1.5

15A-750A

outer attached shunt 75mV 60mV 50mV


KA

1.5

1KA-3KA

outer attached shunt 75mV 60mV 50mV


DC voltmeter

V

1.5

3V-600V

can be directly connected

KV

1.5

1KV-3KV

outer attached resistance value