Product details

Environmental Condition:

Ambient temperature: -40℃~ +40℃;

Altitude: ≤2000m

Wind pressure: ≤700Pa(equals to wind speed 34m/s)

Relative humidity: monthly average 90%, daily average 95%;

Air contamination degree: III degree

Ambient air should not be contaminated by corrosive gases or flammable gases

No frequent violent vibration


Technical Data:

No.

Item

Unit

Data

1

Rated voltage

KV

24

2

Rated current

A

630/1250/1600

3

Rated frequency

HZ

50/60

4

Rated short-circuit breaking current

KA

20,25,31.5

5

Rated peak value withstand current(peak)

KA

50,63,80

6

Rated short time withstand current(4s)

KA

20,25

7

Rated short-circuit closing current (peak)

KA

50,63,80

8

Fixed operation sequence


off-0.3S-on/off-180S on/off

9

Rated short-circuit breaking current breaking number

times

30

10

Mechanical life-span

times

10000


Application:

ZW32-24high voltage vacuum circuitis a outdoor switch equipment of power system which ratingtri-phase AC 50Hz, 24kV.

It is used to make and break load current, overload current and short-circuit current.Act as the protecting and controlling unit for substation and industrial mining enterprises’ equipments. Applicable to locations that need frequent operating in rated current or under repeatedly on/off shortcircuit current.

As the power grid's breaking switch, it can realize the distribution network automation after installation of the controller.


Standards:

GB1984

GB/T28001-2011 idt OHSAS18001:2007

GB/T24001-2004 idt ISO14001:2004


http://www.tyouelectric.com/